Extension cord gauge chart

A 15 amp tool on a 25 ft extension cord needs 14 AWG, and on 100 ft it needs 12 AWG. A 10 amp load needs 16 AWG at 50 ft. The chart keeps the voltage drop at 120 V within 5%.

Extension cord gauge by load in amps and cord length
Load25 ft50 ft100 ft150 ft
5 A (600 W)18 AWG18 AWG16 AWG14 AWG
8 A (960 W)18 AWG16 AWG14 AWG12 AWG
10 A (1,200 W)18 AWG16 AWG12 AWG12 AWG
13 A (1,560 W)16 AWG14 AWG12 AWG10 AWG
15 A (1,800 W)14 AWG14 AWG12 AWG10 AWG

Extension cord ratings by gauge

Extension cord ampacity by gauge for two current-carrying conductors
Cord gaugeRating, amps
18 AWG10 A
16 AWG13 A
14 AWG18 A
12 AWG25 A
10 AWG30 A

Ratings are for a cord with two current-carrying conductors, like a standard three-prong extension cord. A household plug and outlet are rated 15 A, so a cord rated higher still carries no more than 15 A through a standard plug.

How the cord gauge is chosen

Each cell is the thinnest cord rated for the load whose voltage drop at 120 V stays within 5%. A dash means no common cord gauge is enough: move the tool closer to the outlet or use a shorter, heavier cord. The amp rating on the tool's nameplate is the load to look up.