Voltage drop chart
12 AWG copper loaded to 20 A can run 45 ft one way at 120 V before the voltage drop passes 3%, and 91 ft at 240 V. 10 AWG at 30 A reaches 48 ft at 120 V.
| Copper wire | Load | 120 V, 3% | 240 V, 3% | 240 V, 5% |
|---|---|---|---|---|
| 14 AWG | 15 A | 38 ft | 76 ft | 127 ft |
| 12 AWG | 20 A | 45 ft | 91 ft | 151 ft |
| 10 AWG | 30 A | 48 ft | 96 ft | 160 ft |
| 8 AWG | 50 A | 46 ft | 92 ft | 153 ft |
| 6 AWG | 60 A | 61 ft | 122 ft | 203 ft |
| 4 AWG | 80 A | 72 ft | 145 ft | 242 ft |
| 3 AWG | 100 A | 73 ft | 146 ft | 244 ft |
| 2 AWG | 110 A | 84 ft | 168 ft | 280 ft |
| 1 AWG | 125 A | 93 ft | 186 ft | 311 ft |
| 1/0 AWG | 150 A | 98 ft | 196 ft | 327 ft |
| 2/0 AWG | 175 A | 106 ft | 212 ft | 353 ft |
| 3/0 AWG | 200 A | 117 ft | 234 ft | 390 ft |
| 4/0 AWG | 225 A | 131 ft | 262 ft | 437 ft |
- 120 V, 3%
- 240 V, 3%
- 240 V, 5%
How to use the voltage drop chart
Distances are one way, from the panel to the load, with the circuit loaded to the largest breaker the wire can take at 75 °C. At half the load the distance doubles. Aluminum reaches about 60% of the copper distance at the same size.
The 3% target is a common recommendation for a branch circuit, with 5% for the feeder and branch together. Drop is calculated as 2 × K × amps × feet ÷ circular mils, with K = 12.9 for copper.