Voltage drop chart

12 AWG copper loaded to 20 A can run 45 ft one way at 120 V before the voltage drop passes 3%, and 91 ft at 240 V. 10 AWG at 30 A reaches 48 ft at 120 V.

Longest one-way copper run, by wire size loaded to its largest 75 °C breaker, that keeps the voltage drop within 3% at 120 and 240 V or 5% at 240 V
Copper wireLoad120 V, 3%240 V, 3%240 V, 5%
14 AWG15 A38 ft76 ft127 ft
12 AWG20 A45 ft91 ft151 ft
10 AWG30 A48 ft96 ft160 ft
8 AWG50 A46 ft92 ft153 ft
6 AWG60 A61 ft122 ft203 ft
4 AWG80 A72 ft145 ft242 ft
3 AWG100 A73 ft146 ft244 ft
2 AWG110 A84 ft168 ft280 ft
1 AWG125 A93 ft186 ft311 ft
1/0 AWG150 A98 ft196 ft327 ft
2/0 AWG175 A106 ft212 ft353 ft
3/0 AWG200 A117 ft234 ft390 ft
4/0 AWG225 A131 ft262 ft437 ft
010020030040050014106312/04/0Longest run, ftCopper wire, AWG1412108643211/02/03/04/0120 V, 3%240 V, 3%240 V, 5%
  • 120 V, 3%
  • 240 V, 3%
  • 240 V, 5%
Longest one-way run by wire size, each wire at its own 75 °C breaker load.

How to use the voltage drop chart

Distances are one way, from the panel to the load, with the circuit loaded to the largest breaker the wire can take at 75 °C. At half the load the distance doubles. Aluminum reaches about 60% of the copper distance at the same size.

The 3% target is a common recommendation for a branch circuit, with 5% for the feeder and branch together. Drop is calculated as 2 × K × amps × feet ÷ circular mils, with K = 12.9 for copper.