Wire size calculator

A 20 amp, 120 V circuit needs 12 AWG copper by ampacity at 75 °C terminations; at 50 ft one way it needs 10 AWG copper to keep the voltage drop within 3% (2.1%). Enter your own load, distance and voltage below.

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
10 AWG copper

The run is long: ampacity alone allows 12 AWG, but a larger wire keeps the drop within 3%.

Breaker
20 A
Voltage drop
2.5 V (2.1%)
Volts at the load
117.5 V
Ground wire
10 AWG copper

How it is calculated

  1. Breaker: 20 A rounded up to a standard size = 20 A.
  2. Smallest copper conductor rated for 20 A at 75 °C: 12 AWG.
  3. Drop = 2 × K × 20 A × 50 ft ÷ 10,380 cmil = 2.49 V, target 3% of 120 V.
Panel20 A120 V10 AWG copper50 ft one wayLoad117.5 V

How to calculate wire size

Two checks size a circuit wire: the current it must carry (ampacity) and the voltage it loses along the run. The worked numbers use the calculator's defaults: a 20 A, 120 V circuit, 50 ft one way, copper wire and 75 °C terminations.

Step 1: breaker size from the load

Breaker = load current, rounded up to the next standard breaker size

Continuous load (3 hours or more): breaker = load current × 1.25, rounded up

Example A 20 A load that is not continuous: 20 A breaker.

Example The same 20 A as a continuous load: 20 A × 1.25 → 25 A breaker.

Step 2: smallest wire by ampacity at 60 °C or 75 °C

Wire = the smallest size whose ampacity in the termination column (60 °C or 75 °C) is at least the breaker rating

Small copper wires have a lower breaker limit than their ampacity: 14 AWG on 15 A, 12 AWG on 20 A and 10 AWG on 30 A at most

Example 20 A, copper, 75 °C: 12 AWG (25 A in the 75 °C column, protected by 20 A at most).

Step 3: voltage drop on that wire

VD = 2 × K × I × L ÷ cmil for single phase; three phase uses √3 in place of 2

K = 12.9 ohm·cmil/ft for copper and 21.2 for aluminum; I = amps; L = one-way length in feet; cmil = the wire's area in circular mils

Example 12 AWG: 2 × 12.9 × 20 A × 50 ft ÷ 6,530 cmil = 3.95 V.

Step 4: compare the drop with 3% and size up

VD % = VD ÷ circuit volts × 100

Above 3%: repeat step 3 with the next larger size until the drop is within 3%

Example 3.95 V ÷ 120 V × 100 = 3.29%, over 3%, so 12 AWG is too small for 50 ft.

Example 10 AWG: 2 × 12.9 × 20 A × 50 ft ÷ 10,380 cmil = 2.49 V = 2.07%, within 3%. Answer: 10 AWG copper.

Wire size by amps and distance

At 100 ft one way, a 20 A, 120 V circuit needs 8 AWG copper and a 30 A, 240 V circuit needs 8 AWG copper to keep the voltage drop within 3%. The table runs the same two checks as the calculator for common circuits: 15 and 20 A at 120 V, 30 to 60 A at 240 V.

Copper wire size by breaker rating and one-way distance, 75 °C terminations, voltage drop within 3%: 15 and 20 A circuits at 120 V, 30 to 60 A circuits at 240 V
One-way distance15 A, 120 V20 A, 120 V30 A, 240 V40 A, 240 V50 A, 240 V60 A, 240 V
25 ft14 AWG12 AWG10 AWG8 AWG8 AWG6 AWG
50 ft12 AWG10 AWG10 AWG8 AWG8 AWG6 AWG
100 ft8 AWG8 AWG8 AWG8 AWG6 AWG6 AWG
150 ft8 AWG6 AWG8 AWG6 AWG4 AWG4 AWG
200 ft6 AWG4 AWG6 AWG4 AWG4 AWG3 AWG
300 ft4 AWG3 AWG4 AWG3 AWG2 AWG2 AWG
234681012140100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ft15 A, 120 V20 A, 120 V30 A, 240 V50 A, 240 V23468101214050100150200250300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ft15 A, 120 V20 A, 120 V30 A, 240 V50 A, 240 V
  • 15 A, 120 V
  • 20 A, 120 V
  • 30 A, 240 V
  • 50 A, 240 V
Copper wire size by distance within 3% voltage drop.

How the wire size is chosen

Two limits apply to every circuit. The wire must carry the current without overheating, which is its ampacity. And the voltage lost along the run should stay small, usually within 3%, so that motors start and lights do not dim. On short runs ampacity decides the size. On long runs voltage drop does.

The termination rating matters as much as the wire itself. NM-B cable (Romex) is limited to the 60 °C column. Most modern breakers and panels are rated 75 °C. The 90 °C column is used for derating, not for choosing the final size.

When the hot wires are made larger for voltage drop, the ground wire grows in the same proportion. The calculator shows that size with the result.

Embed this calculator

Paste this code into your site or forum post to show the calculator. It works on any page that allows iframes. Preview the widget.