20 amp wire size

A 20 amp circuit needs 12 AWG copper wire with 75 °C terminations. Aluminum wire is not used for circuits this small.

20 amp wire size by termination rating

Wire size for a 20 amp circuit by termination temperature rating (60 °C: NM-B cable; 75 °C: THHN and most breakers), with the ground wire
Termination ratingCopperAluminum
60 °C, NM-B12 AWGcopper only
75 °C, THHN12 AWGcopper only
Ground wire12 AWG—

20 amp wire size by distance at 120 V

Sizes that keep the voltage drop within 3% on a 120 V circuit loaded to the full 20 A, 75 °C terminations. The copper ground wire grows with the hot wires on long runs.

Wire size for a 20 amp, 120 V circuit by one-way distance, keeping the voltage drop within 3%
One-way distanceCopperDropCopper ground
25 ft12 AWG1.6%12 AWG
50 ft10 AWG2.1%10 AWG
100 ft8 AWG2.6%8 AWG
150 ft6 AWG2.5%6 AWG
200 ft4 AWG2.1%4 AWG
300 ft3 AWG2.5%3 AWG
346810120100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopper
Wire size for 20 A at 120 V by distance, within 3% voltage drop.

Check your own 20 amp run

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
10 AWG copper

The run is long: ampacity alone allows 12 AWG, but a larger wire keeps the drop within 3%.

Breaker
20 A
Voltage drop
2.5 V (2.1%)
Volts at the load
117.5 V
Ground wire
10 AWG copper

How it is calculated

  1. Breaker: 20 A rounded up to a standard size = 20 A.
  2. Smallest copper conductor rated for 20 A at 75 °C: 12 AWG.
  3. Drop = 2 × K × 20 A × 50 ft ÷ 10,380 cmil = 2.49 V, target 3% of 120 V.
Panel20 A120 V10 AWG copper50 ft one wayLoad117.5 V

What a 20 amp circuit is used for