15 amp wire size

A 15 amp circuit needs 14 AWG copper wire with 75 °C terminations. Aluminum wire is not used for circuits this small.

15 amp wire size by termination rating

Wire size for a 15 amp circuit by termination temperature rating (60 °C: NM-B cable; 75 °C: THHN and most breakers), with the ground wire
Termination ratingCopperAluminum
60 °C, NM-B14 AWGcopper only
75 °C, THHN14 AWGcopper only
Ground wire14 AWG—

15 amp wire size by distance at 120 V

Sizes that keep the voltage drop within 3% on a 120 V circuit loaded to the full 15 A, 75 °C terminations. The copper ground wire grows with the hot wires on long runs.

Wire size for a 15 amp, 120 V circuit by one-way distance, keeping the voltage drop within 3%
One-way distanceCopperDropCopper ground
25 ft14 AWG2.0%14 AWG
50 ft12 AWG2.5%12 AWG
100 ft8 AWG2.0%8 AWG
150 ft8 AWG2.9%8 AWG
200 ft6 AWG2.5%6 AWG
300 ft4 AWG2.3%4 AWG
4681012140100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopper
Wire size for 15 A at 120 V by distance, within 3% voltage drop.

Check your own 15 amp run

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
12 AWG copper

The run is long: ampacity alone allows 14 AWG, but a larger wire keeps the drop within 3%.

Breaker
15 A
Voltage drop
3.0 V (2.5%)
Volts at the load
117.0 V
Ground wire
12 AWG copper

How it is calculated

  1. Breaker: 15 A rounded up to a standard size = 15 A.
  2. Smallest copper conductor rated for 15 A at 75 °C: 14 AWG.
  3. Drop = 2 × K × 15 A × 50 ft ÷ 6,530 cmil = 2.96 V, target 3% of 120 V.
Panel15 A120 V12 AWG copper50 ft one wayLoad117.0 V