How many amps can 14 gauge wire carry?
14 AWG copper wire carries 15 A at 60 °C, 20 A at 75 °C and 25 A at 90 °C. 14 AWG copper goes on a breaker of up to 15 A in NM-B cable.
14 AWG wire ampacity
| Rating | Copper | Aluminum |
|---|---|---|
| 60 °C, NM-B | 15 A | not made |
| 75 °C | 20 A | not made |
| 90 °C | 25 A | not made |
| Max breaker, 75 °C | 15 A | — |
| As a cord | 18 A | — |
14 AWG copper may be protected by a breaker of no more than 15 A, whatever its ampacity column says.
14 AWG wire size and resistance
| Diameter, AWG nominal | 0.0641 in. / 1.63 mm |
|---|---|
| Area | 4,110 cmil / 2.08 mm² |
| Copper resistance | 3.139 Ω per 1,000 ft |
How far can 14 AWG wire run?
| Load | 120 V | 240 V |
|---|---|---|
| 15 A | 38 ft | 76 ft |
| 8 A | 71 ft | 143 ft |
How many 14 AWG wires fit in conduit
| THHN in | 1/2″ | 3/4″ | 1″ |
|---|---|---|---|
| EMT | 12 | 22 | 35 |
| PVC Sch 40 | 11 | 21 | 34 |
| PVC Sch 80 | 9 | 17 | 28 |
| RMC | 13 | 22 | 36 |
What 14 AWG wire is used for
- Lighting and general outlet circuits
- Medium-duty extension cords
Check a 14 AWG circuit
What are you sizing for?
A
ft
From the panel to the load, not there and back
Voltage
Conductor
Termination rating
Result
14 AWG copper
Ampacity sets the size; the voltage drop is within 3%.
- Breaker
- 15 A
- Voltage drop
- 2.4 V (2.0%)
- Volts at the load
- 117.6 V
- Ground wire
- 14 AWG copper
How it is calculated
- Breaker: 15 A rounded up to a standard size = 15 A.
- Smallest copper conductor rated for 15 A at 60 °C: 14 AWG.
- Drop = 2 × K × 15 A × 25 ft ÷ 4,110 cmil = 2.35 V, target 3% of 120 V.