How many amps can 10 gauge wire carry?
10 AWG copper wire carries 30 A at 60 °C, 35 A at 75 °C and 40 A at 90 °C. 10 AWG copper goes on a breaker of up to 30 A in NM-B cable.
10 AWG wire ampacity
| Rating | Copper | Aluminum |
|---|---|---|
| 60 °C, NM-B | 30 A | 25 A |
| 75 °C | 35 A | 30 A |
| 90 °C | 40 A | 35 A |
| Max breaker, 75 °C | 30 A | 25 A |
| As a cord | 30 A | — |
- Copper
- Aluminum
10 AWG copper may be protected by a breaker of no more than 30 A, whatever its ampacity column says.
10 AWG wire size and resistance
| Diameter, AWG nominal | 0.1019 in. / 2.59 mm |
|---|---|
| Area | 10,380 cmil / 5.26 mm² |
| Copper resistance | 1.243 Ω per 1,000 ft |
How far can 10 AWG wire run?
| Load | 120 V | 240 V |
|---|---|---|
| 30 A | 48 ft | 96 ft |
| 15 A | 96 ft | 193 ft |
How many 10 AWG wires fit in conduit
| THHN in | 1/2″ | 3/4″ | 1″ |
|---|---|---|---|
| EMT | 5 | 10 | 16 |
| PVC Sch 40 | 5 | 9 | 15 |
| PVC Sch 80 | 4 | 7 | 13 |
| RMC | 6 | 10 | 17 |
What 10 AWG wire is used for
- Electric dryer and water heater circuits
- RV hookups and small air conditioners
Check a 10 AWG circuit
What are you sizing for?
A
ft
From the panel to the load, not there and back
Voltage
Conductor
Termination rating
Result
10 AWG copper
Ampacity sets the size; the voltage drop is within 3%.
- Breaker
- 30 A
- Voltage drop
- 3.7 V (1.6%)
- Volts at the load
- 236.3 V
- Ground wire
- 10 AWG copper
How it is calculated
- Breaker: 30 A rounded up to a standard size = 30 A.
- Smallest copper conductor rated for 30 A at 60 °C: 10 AWG.
- Drop = 2 × K × 30 A × 50 ft ÷ 10,380 cmil = 3.73 V, target 3% of 240 V.