How many amps can 6 gauge wire carry?

6 AWG copper is rated 55 A (60 °C), 65 A (75 °C) and 75 A (90 °C), and goes on a breaker of up to 50 A in NM-B cable or 60 A with 75 °C terminations.

6 AWG wire ampacity

6 AWG copper and aluminum ampacity at 60, 75 and 90 °C, up to three current-carrying wires at 30 °C (86 °F) ambient, with the largest breaker at 75 °C
RatingCopperAluminum
60 °C, NM-B55 A40 A
75 °C65 A50 A
90 °C75 A55 A
Max breaker, 75 °C60 A50 A
0255075Ampacity, ARating60 °C, NM-B60 °C, NM-B, Copper: 555560 °C, NM-B, Aluminum: 404075 °C75 °C, Copper: 656575 °C, Aluminum: 505090 °C90 °C, Copper: 757590 °C, Aluminum: 5555
  • Copper
  • Aluminum
6 AWG ampacity by temperature rating.

6 AWG wire size and resistance

6 AWG bare conductor size and copper resistance at operating temperature. The diameter is the nominal AWG value; stranded wire of the same size is slightly larger.
Diameter, AWG nominal0.1620 in. / 4.12 mm
Area26,240 cmil / 13.3 mm²
Copper resistance0.492 Ω per 1,000 ft

How far can 6 AWG wire run?

Longest one-way 6 AWG copper run within 3% voltage drop, at the full 60 A breaker load and at half load, at 120 and 240 V
Load120 V240 V
60 A61 ft122 ft
30 A122 ft244 ft

How many 6 AWG wires fit in conduit

Maximum number of 6 AWG THHN wires by conduit type and trade size, at 40% fill for three or more wires
THHN in3/4″1″1-1/4″
EMT4712
PVC Sch 404611
PVC Sch 80359
RMC4712

What 6 AWG wire is used for

Check a 6 AWG circuit

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
6 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
50 A
Voltage drop
2.5 V (1.0%)
Volts at the load
237.5 V
Ground wire
10 AWG copper

How it is calculated

  1. Breaker: 50 A rounded up to a standard size = 50 A.
  2. Smallest copper conductor rated for 50 A at 60 °C: 6 AWG.
  3. Drop = 2 × K × 50 A × 50 ft ÷ 26,240 cmil = 2.46 V, target 3% of 240 V.
Panel50 A240 V6 AWG copper50 ft one wayLoad237.5 V