How many amps can 6 gauge wire carry?
6 AWG copper is rated 55 A (60 °C), 65 A (75 °C) and 75 A (90 °C), and goes on a breaker of up to 50 A in NM-B cable or 60 A with 75 °C terminations.
6 AWG wire ampacity
| Rating | Copper | Aluminum |
|---|---|---|
| 60 °C, NM-B | 55 A | 40 A |
| 75 °C | 65 A | 50 A |
| 90 °C | 75 A | 55 A |
| Max breaker, 75 °C | 60 A | 50 A |
- Copper
- Aluminum
6 AWG wire size and resistance
| Diameter, AWG nominal | 0.1620 in. / 4.12 mm |
|---|---|
| Area | 26,240 cmil / 13.3 mm² |
| Copper resistance | 0.492 Ω per 1,000 ft |
How far can 6 AWG wire run?
| Load | 120 V | 240 V |
|---|---|---|
| 60 A | 61 ft | 122 ft |
| 30 A | 122 ft | 244 ft |
How many 6 AWG wires fit in conduit
| THHN in | 3/4″ | 1″ | 1-1/4″ |
|---|---|---|---|
| EMT | 4 | 7 | 12 |
| PVC Sch 40 | 4 | 6 | 11 |
| PVC Sch 80 | 3 | 5 | 9 |
| RMC | 4 | 7 | 12 |
What 6 AWG wire is used for
- Electric ranges and EV chargers
- Feeders to small sub panels
Check a 6 AWG circuit
What are you sizing for?
A
ft
From the panel to the load, not there and back
Voltage
Conductor
Termination rating
Result
6 AWG copper
Ampacity sets the size; the voltage drop is within 3%.
- Breaker
- 50 A
- Voltage drop
- 2.5 V (1.0%)
- Volts at the load
- 237.5 V
- Ground wire
- 10 AWG copper
How it is calculated
- Breaker: 50 A rounded up to a standard size = 50 A.
- Smallest copper conductor rated for 50 A at 60 °C: 6 AWG.
- Drop = 2 × K × 50 A × 50 ft ÷ 26,240 cmil = 2.46 V, target 3% of 240 V.