How many amps can 4 gauge wire carry?
4 AWG copper is rated 70 A (60 °C), 85 A (75 °C) and 95 A (90 °C), and goes on a breaker of up to 70 A in NM-B cable or 80 A with 75 °C terminations.
4 AWG wire ampacity
| Rating | Copper | Aluminum |
|---|---|---|
| 60 °C, NM-B | 70 A | 55 A |
| 75 °C | 85 A | 65 A |
| 90 °C | 95 A | 75 A |
| Max breaker, 75 °C | 80 A | 60 A |
- Copper
- Aluminum
4 AWG wire size and resistance
| Diameter, AWG nominal | 0.2043 in. / 5.19 mm |
|---|---|
| Area | 41,740 cmil / 21.2 mm² |
| Copper resistance | 0.309 Ω per 1,000 ft |
How far can 4 AWG wire run?
| Load | 120 V | 240 V |
|---|---|---|
| 80 A | 72 ft | 145 ft |
| 40 A | 145 ft | 291 ft |
How many 4 AWG wires fit in conduit
| THHN in | 1″ | 1-1/4″ | 1-1/2″ |
|---|---|---|---|
| EMT | 4 | 7 | 10 |
| PVC Sch 40 | 4 | 7 | 9 |
| PVC Sch 80 | 3 | 6 | 8 |
| RMC | 4 | 7 | 10 |
What 4 AWG wire is used for
- Feeders to sub panels
- Service entrance conductors for small houses
Check a 4 AWG circuit
What are you sizing for?
A
ft
From the panel to the load, not there and back
Voltage
Conductor
Termination rating
Result
4 AWG copper
Ampacity sets the size; the voltage drop is within 3%.
- Breaker
- 70 A
- Voltage drop
- 2.2 V (0.9%)
- Volts at the load
- 237.8 V
- Ground wire
- 8 AWG copper
How it is calculated
- Breaker: 70 A rounded up to a standard size = 70 A.
- Smallest copper conductor rated for 70 A at 60 °C: 4 AWG.
- Drop = 2 × K × 70 A × 50 ft ÷ 41,740 cmil = 2.16 V, target 3% of 240 V.