50 amp wire size

A 50 amp circuit needs 8 AWG copper or 6 AWG aluminum wire with 75 °C terminations. In NM-B cable (Romex), which is limited to the 60 °C column, a 50 amp circuit needs 6 AWG copper.

50 amp wire size by termination rating

Wire size for a 50 amp circuit by termination temperature rating (60 °C: NM-B cable; 75 °C: THHN and most breakers), with the ground wire
Termination ratingCopperAluminum
60 °C, NM-B6 AWG4 AWG
75 °C, THHN8 AWG6 AWG
Ground wire10 AWG8 AWG

50 amp wire size by distance at 240 V

Sizes that keep the voltage drop within 3% on a 240 V circuit loaded to the full 50 A, 75 °C terminations. The copper ground wire grows with the hot wires on long runs.

Wire size for a 50 amp, 240 V circuit by one-way distance, keeping the voltage drop within 3%
One-way distanceCopperDropCopper groundAluminumDrop
25 ft8 AWG0.8%10 AWG6 AWG0.8%
50 ft8 AWG1.6%10 AWG6 AWG1.7%
100 ft6 AWG2.0%8 AWG4 AWG2.1%
150 ft4 AWG1.9%4 AWG3 AWG2.5%
200 ft4 AWG2.6%4 AWG2 AWG2.7%
300 ft2 AWG2.4%4 AWG1/0 AWG2.5%
1/01234680100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum1/0123468050100150200250300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum
  • Copper
  • Aluminum
Wire size for 50 A at 240 V by distance, within 3% voltage drop.

Check your own 50 amp run

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
8 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
50 A
Voltage drop
3.9 V (1.6%)
Volts at the load
236.1 V
Ground wire
10 AWG copper

How it is calculated

  1. Breaker: 50 A rounded up to a standard size = 50 A.
  2. Smallest copper conductor rated for 50 A at 75 °C: 8 AWG.
  3. Drop = 2 × K × 50 A × 50 ft ÷ 16,510 cmil = 3.91 V, target 3% of 240 V.
Panel50 A240 V8 AWG copper50 ft one wayLoad236.1 V