60 amp wire size

60 amp wire size: 6 AWG copper or 4 AWG aluminum, with 75 °C terminations. In NM-B cable (Romex), which is limited to the 60 °C column, a 60 amp circuit needs 4 AWG copper.

60 amp wire size by termination rating

Wire size for a 60 amp circuit by termination temperature rating (60 °C: NM-B cable; 75 °C: THHN and most breakers), with the ground wire
Termination ratingCopperAluminum
60 °C, NM-B4 AWG3 AWG
75 °C, THHN6 AWG4 AWG
Ground wire10 AWG8 AWG

60 amp wire size by distance at 240 V

Sizes that keep the voltage drop within 3% on a 240 V circuit loaded to the full 60 A, 75 °C terminations. The copper ground wire grows with the hot wires on long runs.

Wire size for a 60 amp, 240 V circuit by one-way distance, keeping the voltage drop within 3%
One-way distanceCopperDropCopper groundAluminumDrop
25 ft6 AWG0.6%10 AWG4 AWG0.6%
50 ft6 AWG1.2%10 AWG4 AWG1.3%
100 ft6 AWG2.5%10 AWG4 AWG2.5%
150 ft4 AWG2.3%6 AWG2 AWG2.4%
200 ft3 AWG2.5%6 AWG1 AWG2.5%
300 ft2 AWG2.9%4 AWG2/0 AWG2.4%
2/01/0123460100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum2/01/012346050100150200250300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum
  • Copper
  • Aluminum
Wire size for 60 A at 240 V by distance, within 3% voltage drop.

Check your own 60 amp run

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
6 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
60 A
Voltage drop
2.9 V (1.2%)
Volts at the load
237.1 V
Ground wire
10 AWG copper

How it is calculated

  1. Breaker: 60 A rounded up to a standard size = 60 A.
  2. Smallest copper conductor rated for 60 A at 75 °C: 6 AWG.
  3. Drop = 2 × K × 60 A × 50 ft ÷ 26,240 cmil = 2.95 V, target 3% of 240 V.
Panel60 A240 V6 AWG copper50 ft one wayLoad237.1 V

What a 60 amp circuit is used for