Wire size for a 60 amp sub panel

Feed a 60 amp sub panel with 6 AWG copper or 4 AWG aluminum wire at 75 °C and a separate 10 AWG copper (8 AWG aluminum) ground.

60 amp sub panel feeder size

60 amp sub panel feeder at 75 °C and ground wire, copper and aluminum, and the smallest conduit for four THHN wires
CopperAluminum
Feeder, 75 °C6 AWG4 AWG
NM-B, 60 °C4 AWG—
Ground wire10 AWG8 AWG
EMT conduit3/4″1″
PVC 40 conduit3/4″1″

Conduit sizes are for four THHN wires: two hots and a neutral of the feeder size plus the ground wire.

60 amp sub panel wire size by distance

Sizes that keep the voltage drop within 3% at 240 V with the panel fully loaded. When the feeder is made larger for distance, the ground wire grows with it, in copper and in aluminum.

60 amp sub panel feeder and ground wire by one-way distance, copper and aluminum at 75 °C, within 3% voltage drop at 240 V and full load
DistanceCopper feederCopper groundAluminum feederAluminum ground
50 ft6 AWG10 AWG4 AWG8 AWG
100 ft6 AWG10 AWG4 AWG8 AWG
150 ft4 AWG6 AWG2 AWG4 AWG
200 ft3 AWG6 AWG1 AWG4 AWG
300 ft2 AWG4 AWG2/0 AWG2 AWG
2/01/0123460100200300Feeder size, AWG / kcmilOne-way distance, ft50 ft100 ft150 ft200 ft300 ftCopper feederAluminum feeder2/01/012346050100150200250300Feeder size, AWG / kcmilOne-way distance, ft50 ft100 ft150 ft200 ft300 ftCopper feederAluminum feeder
  • Copper feeder
  • Aluminum feeder
60 amp sub panel feeder size by distance, within 3% voltage drop at 240 V.

A panel is rarely loaded to its full rating for long. Sizing for the actual calculated load instead of the breaker rating gives smaller wire on long runs; the calculator below does that.

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
6 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
60 A
Voltage drop
5.9 V (2.5%)
Volts at the load
234.1 V
Ground wire
10 AWG copper

How it is calculated

  1. Breaker: 60 A rounded up to a standard size = 60 A.
  2. Smallest copper conductor rated for 60 A at 75 °C: 6 AWG.
  3. Drop = 2 × K × 60 A × 100 ft ÷ 26,240 cmil = 5.90 V, target 3% of 240 V.
Panel60 A240 V6 AWG copper100 ft one wayLoad234.1 V