Ground wire size chart

A 20 amp circuit needs a 12 AWG copper ground wire, a 60 amp circuit 10 AWG, a 100 amp circuit 8 AWG and a 200 amp circuit 6 AWG copper. Aluminum ground wires are one or two sizes larger.

Minimum equipment grounding conductor size by breaker rating, copper and aluminum
Breaker up toCopperAluminum
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1,000 A2/0 AWG4/0 AWG
1,200 A3/0 AWG250 kcmil
2503/01/024812201003005008001,200Ground wire, AWG / kcmilBreaker up to, A1520601002003004005006008001,0001,200CopperAluminum
  • Copper
  • Aluminum
Smallest ground wire by breaker rating.

How to read the ground wire size chart

Find the first row at or above the breaker that protects the circuit. A 30 or 45 amp circuit uses the 60 A row. The ground wire never needs to be larger than the circuit's hot wires.

Ground wire on long runs

When the hot wires are made larger than ampacity requires, usually for voltage drop, the ground wire must grow in the same proportion of circular mils. For example, a 100 A copper feeder upsized from 3 AWG to 1/0 AWG needs a 4 AWG copper ground instead of 8 AWG. The wire size calculator does this automatically.