Wire size chart

A 20 amp circuit needs 12 AWG copper, a 30 amp circuit 10 AWG and a 50 amp circuit 8 AWG copper with 75 °C terminations (6 AWG in NM-B cable). The chart lists every standard breaker from 15 to 400 amps.

Wire size by breaker rating: copper in NM-B cable (60 °C) and at 75 °C, aluminum at 75 °C
BreakerCopper NM-B (60 °C)Copper 75 °CAluminum 75 °C
15 A14 AWG14 AWGcopper only
20 A12 AWG12 AWGcopper only
25 A10 AWG10 AWGcopper only
30 A10 AWG10 AWGcopper only
35 A8 AWG8 AWG8 AWG
40 A8 AWG8 AWG8 AWG
45 A6 AWG8 AWG6 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
90 A2 AWG3 AWG2 AWG
100 Anot made3 AWG1 AWG
110 Anot made2 AWG1/0 AWG
125 Anot made1 AWG2/0 AWG
150 Anot made1/0 AWG3/0 AWG
175 Anot made2/0 AWG4/0 AWG
200 Anot made3/0 AWG250 kcmil
225 Anot made4/0 AWG300 kcmil
250 Anot made250 kcmil350 kcmil
300 Anot made350 kcmil500 kcmil
350 Anot made500 kcmil—
400 A—600 kcmil—
6003504/01/038140100200300400Wire size, AWG / kcmilBreaker, A15 A20 A25 A30 A35 A40 A45 A50 A60 A70 A80 A90 A100 A110 A125 A150 A175 A200 A225 A250 A300 A350 A400 ACopper NM-B (60 °C)Copper 75 °CAluminum 75 °C
  • Copper NM-B (60 °C)
  • Copper 75 °C
  • Aluminum 75 °C
Smallest wire size by breaker rating.

How the wire size chart is built

Each size is the smallest conductor whose ampacity, capped by the small-conductor limits, is at least the breaker rating. "Not made" in the NM-B column means NM-B cable is not sold in that size; use the 75 °C column for wire in conduit or SE/SER cable with 75 °C terminations. Aluminum is not used for circuits that need copper smaller than 8 AWG. A dash means no size up to 600 kcmil is enough.

Long runs need larger wire

The chart sizes for heat only. On a long run the voltage drop can call for a bigger wire; the wire size calculator checks both.