Breaker size chart
14 AWG copper wire takes a breaker of up to 15 A, 12 AWG up to 20 A, 10 AWG up to 30 A and 8 AWG up to 50 A with 75 °C terminations (40 A in NM-B cable).
| Wire size | Copper 60 °C | Copper 75 °C | Aluminum 60 °C | Aluminum 75 °C |
|---|---|---|---|---|
| 14 AWG | 15 A | 15 A | — | — |
| 12 AWG | 20 A | 20 A | 15 A | 15 A |
| 10 AWG | 30 A | 30 A | 25 A | 25 A |
| 8 AWG | 40 A | 50 A | 35 A | 40 A |
| 6 AWG | 50 A | 60 A | 40 A | 50 A |
| 4 AWG | 70 A | 80 A | 50 A | 60 A |
| 3 AWG | 80 A | 100 A | 60 A | 70 A |
| 2 AWG | 90 A | 110 A | 70 A | 90 A |
| 1 AWG | 110 A | 125 A | 80 A | 100 A |
| 1/0 AWG | 125 A | 150 A | 100 A | 110 A |
| 2/0 AWG | 125 A | 175 A | 110 A | 125 A |
| 3/0 AWG | 150 A | 200 A | 125 A | 150 A |
| 4/0 AWG | 175 A | 225 A | 150 A | 175 A |
| 250 kcmil | 200 A | 250 A | 150 A | 200 A |
| 300 kcmil | 225 A | 250 A | 175 A | 225 A |
| 350 kcmil | 250 A | 300 A | 200 A | 250 A |
| 400 kcmil | 250 A | 300 A | 225 A | 250 A |
| 500 kcmil | 300 A | 350 A | 250 A | 300 A |
| 600 kcmil | 350 A | 400 A | 250 A | 300 A |
- Copper 60 °C
- Copper 75 °C
- Aluminum 60 °C
- Aluminum 75 °C
How the breaker size chart works
Each value is the largest standard breaker that does not exceed the wire's ampacity, after the small-conductor limits for 14, 12 and 10 AWG. In some cases the code allows the next standard size up when the ampacity falls between two breaker sizes; this chart does not apply that allowance, so it errs on the safe side.
Motor circuits, air conditioners and other equipment with a nameplate maximum breaker follow their own rules: use the size printed on the nameplate.