Breaker size chart

14 AWG copper wire takes a breaker of up to 15 A, 12 AWG up to 20 A, 10 AWG up to 30 A and 8 AWG up to 50 A with 75 °C terminations (40 A in NM-B cable).

Largest standard breaker for each copper and aluminum wire size at 60 °C and 75 °C terminations; NM-B cable uses the copper 60 °C column and is made up to 2 AWG
Wire sizeCopper 60 °CCopper 75 °CAluminum 60 °CAluminum 75 °C
14 AWG15 A15 A——
12 AWG20 A20 A15 A15 A
10 AWG30 A30 A25 A25 A
8 AWG40 A50 A35 A40 A
6 AWG50 A60 A40 A50 A
4 AWG70 A80 A50 A60 A
3 AWG80 A100 A60 A70 A
2 AWG90 A110 A70 A90 A
1 AWG110 A125 A80 A100 A
1/0 AWG125 A150 A100 A110 A
2/0 AWG125 A175 A110 A125 A
3/0 AWG150 A200 A125 A150 A
4/0 AWG175 A225 A150 A175 A
250 kcmil200 A250 A150 A200 A
300 kcmil225 A250 A175 A225 A
350 kcmil250 A300 A200 A250 A
400 kcmil250 A300 A225 A250 A
500 kcmil300 A350 A250 A300 A
600 kcmil350 A400 A250 A300 A
010020030040014106312/04/0300400600Largest breaker, AWire size, AWG / kcmil1412108643211/02/03/04/0250300350400500600Copper 60 °CCopper 75 °CAluminum 60 °CAluminum 75 °C
  • Copper 60 °C
  • Copper 75 °C
  • Aluminum 60 °C
  • Aluminum 75 °C
Largest breaker by wire size.

How the breaker size chart works

Each value is the largest standard breaker that does not exceed the wire's ampacity, after the small-conductor limits for 14, 12 and 10 AWG. In some cases the code allows the next standard size up when the ampacity falls between two breaker sizes; this chart does not apply that allowance, so it errs on the safe side.

Motor circuits, air conditioners and other equipment with a nameplate maximum breaker follow their own rules: use the size printed on the nameplate.