How many amps can 2 gauge wire carry?
2 AWG copper is rated 95 A (60 °C), 115 A (75 °C) and 130 A (90 °C), and goes on a breaker of up to 90 A in NM-B cable or 110 A with 75 °C terminations.
2 AWG wire ampacity
| Rating | Copper | Aluminum |
|---|---|---|
| 60 °C, NM-B | 95 A | 75 A |
| 75 °C | 115 A | 90 A |
| 90 °C | 130 A | 100 A |
| Max breaker, 75 °C | 110 A | 90 A |
- Copper
- Aluminum
2 AWG wire size and resistance
| Diameter, AWG nominal | 0.2576 in. / 6.54 mm |
|---|---|
| Area | 66,360 cmil / 33.6 mm² |
| Copper resistance | 0.194 Ω per 1,000 ft |
How far can 2 AWG wire run?
| Load | 120 V | 240 V |
|---|---|---|
| 110 A | 84 ft | 168 ft |
| 55 A | 168 ft | 336 ft |
How many 2 AWG wires fit in conduit
| THHN in | 1″ | 1-1/4″ | 1-1/2″ |
|---|---|---|---|
| EMT | 3 | 5 | 7 |
| PVC Sch 40 | 3 | 5 | 7 |
| PVC Sch 80 | 1 | 4 | 6 |
| RMC | 3 | 5 | 7 |
What 2 AWG wire is used for
- Feeders to sub panels and detached buildings
- Service entrance conductors
Check a 2 AWG circuit
What are you sizing for?
A
ft
From the panel to the load, not there and back
Voltage
Conductor
Termination rating
Result
2 AWG copper
Ampacity sets the size; the voltage drop is within 3%.
- Breaker
- 90 A
- Voltage drop
- 1.7 V (0.7%)
- Volts at the load
- 238.3 V
- Ground wire
- 8 AWG copper
How it is calculated
- Breaker: 90 A rounded up to a standard size = 90 A.
- Smallest copper conductor rated for 90 A at 60 °C: 2 AWG.
- Drop = 2 × K × 90 A × 50 ft ÷ 66,360 cmil = 1.75 V, target 3% of 240 V.