How many amps can 2 gauge wire carry?

2 AWG copper is rated 95 A (60 °C), 115 A (75 °C) and 130 A (90 °C), and goes on a breaker of up to 90 A in NM-B cable or 110 A with 75 °C terminations.

2 AWG wire ampacity

2 AWG copper and aluminum ampacity at 60, 75 and 90 °C, up to three current-carrying wires at 30 °C (86 °F) ambient, with the largest breaker at 75 °C
RatingCopperAluminum
60 °C, NM-B95 A75 A
75 °C115 A90 A
90 °C130 A100 A
Max breaker, 75 °C110 A90 A
050100150Ampacity, ARating60 °C, NM-B60 °C, NM-B, Copper: 959560 °C, NM-B, Aluminum: 757575 °C75 °C, Copper: 11511575 °C, Aluminum: 909090 °C90 °C, Copper: 13013090 °C, Aluminum: 100100
  • Copper
  • Aluminum
2 AWG ampacity by temperature rating.

2 AWG wire size and resistance

2 AWG bare conductor size and copper resistance at operating temperature. The diameter is the nominal AWG value; stranded wire of the same size is slightly larger.
Diameter, AWG nominal0.2576 in. / 6.54 mm
Area66,360 cmil / 33.6 mm²
Copper resistance0.194 Ω per 1,000 ft

How far can 2 AWG wire run?

Longest one-way 2 AWG copper run within 3% voltage drop, at the full 110 A breaker load and at half load, at 120 and 240 V
Load120 V240 V
110 A84 ft168 ft
55 A168 ft336 ft

How many 2 AWG wires fit in conduit

Maximum number of 2 AWG THHN wires by conduit type and trade size, at 40% fill for three or more wires
THHN in1″1-1/4″1-1/2″
EMT357
PVC Sch 40357
PVC Sch 80146
RMC357

What 2 AWG wire is used for

Check a 2 AWG circuit

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
2 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
90 A
Voltage drop
1.7 V (0.7%)
Volts at the load
238.3 V
Ground wire
8 AWG copper

How it is calculated

  1. Breaker: 90 A rounded up to a standard size = 90 A.
  2. Smallest copper conductor rated for 90 A at 60 °C: 2 AWG.
  3. Drop = 2 × K × 90 A × 50 ft ÷ 66,360 cmil = 1.75 V, target 3% of 240 V.
Panel90 A240 V2 AWG copper50 ft one wayLoad238.3 V