Wire ampacity chart

12 AWG copper is rated 20 A at 60 °C, 25 A at 75 °C and 30 A at 90 °C, but it may be protected by a breaker of no more than 20 A. Use the column that matches the lowest temperature rating in the circuit.

Ampacity of copper and aluminum wire in amps at 60, 75 and 90 °C, up to three current-carrying conductors at 30 °C (86 °F) ambient
SizeCopper 60 °C, ACopper 75 °C, ACopper 90 °C, AAluminum 60 °C, AAluminum 75 °C, AAluminum 90 °C, ASmall-wire breaker limit Cu / Al
14 AWG152025———15 / n/a
12 AWG20253015202520 / 15
10 AWG30354025303530 / 25
8 AWG405055354045—
6 AWG556575405055—
4 AWG708595556575—
3 AWG85100115657585—
2 AWG951151307590100—
1 AWG11013014585100115—
1/0 AWG125150170100120135—
2/0 AWG145175195115135150—
3/0 AWG165200225130155175—
4/0 AWG195230260150180205—
250 kcmil215255290170205230—
300 kcmil240285320195230260—
350 kcmil260310350210250280—
400 kcmil280335380225270305—
500 kcmil320380430260310350—
600 kcmil350420475285340385—
010020030040050014106312/04/0300400600Ampacity, AWire size, AWG / kcmil1412108643211/02/03/04/0250300350400500600Copper 60 °CCopper 75 °CCopper 90 °CAluminum 60 °CAluminum 75 °CAluminum 90 °C01002003004005001412108643211/02/03/04/0250300350400500600Ampacity, AWire size, AWG / kcmil1412108643211/02/03/04/0250300350400500600Copper 60 °CCopper 75 °CCopper 90 °CAluminum 60 °CAluminum 75 °CAluminum 90 °C
  • Copper 60 °C
  • Copper 75 °C
  • Copper 90 °C
  • Aluminum 60 °C
  • Aluminum 75 °C
  • Aluminum 90 °C
Ampacity by wire size, copper and aluminum at 60, 75 and 90 °C.

Which ampacity column to use

Values are for up to three current-carrying conductors in a raceway or cable at 30 °C (86 °F) ambient. NM-B cable is limited to the 60 °C column. THHN in conduit can use the 75 °C column when the breaker, panel and device terminals are all rated 75 °C. The 90 °C column is the starting point for derating in hot locations or crowded conduits, not a rating to size a breaker from.

Small-conductor breaker limits

The last column shows breaker limits that apply regardless of the ampacity column. Sizes without a value there are protected according to their ampacity.