Motor FLA chart
A 1 hp single-phase motor draws 8 A at 230 V and a 5 hp motor 28 A. A 10 hp three-phase motor draws 14 A at 460 V. The branch circuit wire must carry 125% of the full-load amps: 35 A for the 5 hp motor.
Single-phase motor full-load amps
| hp | 115 V | 200 V | 208 V | 230 V | 125% at 230 V |
|---|---|---|---|---|---|
| 1/6 | 4.4 | 2.5 | 2.4 | 2.2 | 2.8 |
| 1/4 | 5.8 | 3.3 | 3.2 | 2.9 | 3.6 |
| 1/3 | 7.2 | 4.1 | 4 | 3.6 | 4.5 |
| 1/2 | 9.8 | 5.6 | 5.4 | 4.9 | 6.1 |
| 3/4 | 13.8 | 7.9 | 7.6 | 6.9 | 8.6 |
| 1 | 16 | 9.2 | 8.8 | 8 | 10 |
| 1-1/2 | 20 | 11.5 | 11 | 10 | 12.5 |
| 2 | 24 | 13.8 | 13.2 | 12 | 15 |
| 3 | 34 | 19.6 | 18.7 | 17 | 21.3 |
| 5 | 56 | 32.2 | 30.8 | 28 | 35 |
| 7-1/2 | 80 | 46 | 44 | 40 | 50 |
| 10 | 100 | 57.5 | 55 | 50 | 62.5 |
- 115 V
- 230 V
Three-phase motor full-load amps
| hp | 200 V | 208 V | 230 V | 460 V | 575 V | 125% at 460 V |
|---|---|---|---|---|---|---|
| 1/2 | 2.5 | 2.4 | 2.2 | 1.1 | 0.9 | 1.4 |
| 3/4 | 3.7 | 3.5 | 3.2 | 1.6 | 1.3 | 2 |
| 1 | 4.8 | 4.6 | 4.2 | 2.1 | 1.7 | 2.6 |
| 1-1/2 | 6.9 | 6.6 | 6 | 3 | 2.4 | 3.8 |
| 2 | 7.8 | 7.5 | 6.8 | 3.4 | 2.7 | 4.3 |
| 3 | 11 | 10.6 | 9.6 | 4.8 | 3.9 | 6 |
| 5 | 17.5 | 16.7 | 15.2 | 7.6 | 6.1 | 9.5 |
| 7-1/2 | 25.3 | 24.2 | 22 | 11 | 9 | 13.8 |
| 10 | 32.2 | 30.8 | 28 | 14 | 11 | 17.5 |
| 15 | 48.3 | 46.2 | 42 | 21 | 17 | 26.3 |
| 20 | 62.1 | 59.4 | 54 | 27 | 22 | 33.8 |
| 25 | 78.2 | 74.8 | 68 | 34 | 27 | 42.5 |
| 30 | 92 | 88 | 80 | 40 | 32 | 50 |
| 40 | 120 | 114 | 104 | 52 | 41 | 65 |
| 50 | 150 | 143 | 130 | 65 | 52 | 81.3 |
| 60 | 177 | 169 | 154 | 77 | 62 | 96.3 |
| 75 | 221 | 211 | 192 | 96 | 77 | 120 |
| 100 | 285 | 273 | 248 | 124 | 99 | 155 |
- 230 V
- 460 V
Table amps versus nameplate amps
Branch circuit conductors, breakers and disconnects are sized from these table values, not from the nameplate. The nameplate current (FLA) is used to set the motor's overload protection. Three-phase values are for induction motors at normal speed.