How many amps can 8 gauge wire carry?
8 AWG copper is rated 40 A (60 °C), 50 A (75 °C) and 55 A (90 °C), and goes on a breaker of up to 40 A in NM-B cable or 50 A with 75 °C terminations.
8 AWG wire ampacity
| Rating | Copper | Aluminum |
|---|---|---|
| 60 °C, NM-B | 40 A | 35 A |
| 75 °C | 50 A | 40 A |
| 90 °C | 55 A | 45 A |
| Max breaker, 75 °C | 50 A | 40 A |
- Copper
- Aluminum
8 AWG wire size and resistance
| Diameter, AWG nominal | 0.1285 in. / 3.26 mm |
|---|---|
| Area | 16,510 cmil / 8.37 mm² |
| Copper resistance | 0.781 Ω per 1,000 ft |
How far can 8 AWG wire run?
| Load | 120 V | 240 V |
|---|---|---|
| 50 A | 46 ft | 92 ft |
| 25 A | 92 ft | 184 ft |
How many 8 AWG wires fit in conduit
| THHN in | 1/2″ | 3/4″ | 1″ |
|---|---|---|---|
| EMT | 3 | 6 | 9 |
| PVC Sch 40 | 3 | 5 | 9 |
| PVC Sch 80 | 1 | 4 | 7 |
| RMC | 3 | 6 | 9 |
What 8 AWG wire is used for
- Cooktops and wall ovens
- Air conditioners and heat pumps
Check a 8 AWG circuit
What are you sizing for?
A
ft
From the panel to the load, not there and back
Voltage
Conductor
Termination rating
Result
8 AWG copper
Ampacity sets the size; the voltage drop is within 3%.
- Breaker
- 40 A
- Voltage drop
- 3.1 V (1.3%)
- Volts at the load
- 236.9 V
- Ground wire
- 10 AWG copper
How it is calculated
- Breaker: 40 A rounded up to a standard size = 40 A.
- Smallest copper conductor rated for 40 A at 60 °C: 8 AWG.
- Drop = 2 × K × 40 A × 50 ft ÷ 16,510 cmil = 3.13 V, target 3% of 240 V.