100 amp wire size

For 100 amps, use 3 AWG copper or 1 AWG aluminum wire when the breaker and terminals are rated 75 °C. As the main service wire of a house, a 100 amp service may use 4 AWG copper or 2 AWG aluminum under the 83% rule: see 100 amp service wire size.

100 amp wire size by termination rating

Wire size for a 100 amp circuit by termination temperature rating (60 °C: NM-B cable; 75 °C: THHN and most breakers), with the ground wire
Termination ratingCopperAluminum
60 °C1 AWG1/0 AWG
75 °C, THHN3 AWG1 AWG
Ground wire8 AWG6 AWG

100 amp wire size by distance at 240 V

Sizes that keep the voltage drop within 3% on a 240 V circuit loaded to the full 100 A, 75 °C terminations. The copper ground wire grows with the hot wires on long runs.

Wire size for a 100 amp, 240 V circuit by one-way distance, keeping the voltage drop within 3%
One-way distanceCopperDropCopper groundAluminumDrop
25 ft3 AWG0.5%8 AWG1 AWG0.5%
50 ft3 AWG1.0%8 AWG1 AWG1.1%
100 ft3 AWG2.0%8 AWG1 AWG2.1%
150 ft2 AWG2.4%6 AWG1/0 AWG2.5%
200 ft1 AWG2.6%4 AWG2/0 AWG2.7%
300 ft2/0 AWG2.4%3 AWG4/0 AWG2.5%
4/03/02/01/01230100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum4/03/02/01/0123050100150200250300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum
  • Copper
  • Aluminum
Wire size for 100 A at 240 V by distance, within 3% voltage drop.

Check your own 100 amp run

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
3 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
100 A
Voltage drop
2.5 V (1.0%)
Volts at the load
237.5 V
Ground wire
8 AWG copper

How it is calculated

  1. Breaker: 100 A rounded up to a standard size = 100 A.
  2. Smallest copper conductor rated for 100 A at 75 °C: 3 AWG.
  3. Drop = 2 × K × 100 A × 50 ft ÷ 52,620 cmil = 2.45 V, target 3% of 240 V.
Panel100 A240 V3 AWG copper50 ft one wayLoad237.5 V