125 amp wire size

125 amp wire size: 1 AWG copper or 2/0 AWG aluminum, with 75 °C terminations. As the main service wire of a house, a 125 amp service may use 2 AWG copper or 1/0 AWG aluminum under the 83% rule: see 125 amp service wire size.

125 amp wire size by termination rating

Wire size for a 125 amp circuit by termination temperature rating (60 °C: NM-B cable; 75 °C: THHN and most breakers), with the ground wire
Termination ratingCopperAluminum
60 °C1/0 AWG3/0 AWG
75 °C, THHN1 AWG2/0 AWG
Ground wire6 AWG4 AWG

125 amp wire size by distance at 240 V

Sizes that keep the voltage drop within 3% on a 240 V circuit loaded to the full 125 A, 75 °C terminations. The copper ground wire grows with the hot wires on long runs.

Wire size for a 125 amp, 240 V circuit by one-way distance, keeping the voltage drop within 3%
One-way distanceCopperDropCopper groundAluminumDrop
25 ft1 AWG0.4%6 AWG2/0 AWG0.4%
50 ft1 AWG0.8%6 AWG2/0 AWG0.8%
100 ft1 AWG1.6%6 AWG2/0 AWG1.7%
150 ft1 AWG2.4%6 AWG2/0 AWG2.5%
200 ft1/0 AWG2.5%4 AWG3/0 AWG2.6%
300 ft3/0 AWG2.4%3 AWG250 kcmil2.7%
2504/03/02/01/010100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum2504/03/02/01/01050100150200250300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum
  • Copper
  • Aluminum
Wire size for 125 A at 240 V by distance, within 3% voltage drop.

Check your own 125 amp run

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
1 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
125 A
Voltage drop
1.9 V (0.8%)
Volts at the load
238.1 V
Ground wire
6 AWG copper

How it is calculated

  1. Breaker: 125 A rounded up to a standard size = 125 A.
  2. Smallest copper conductor rated for 125 A at 75 °C: 1 AWG.
  3. Drop = 2 × K × 125 A × 50 ft ÷ 83,690 cmil = 1.93 V, target 3% of 240 V.
Panel125 A240 V1 AWG copper50 ft one wayLoad238.1 V