150 amp wire size

A 150 amp circuit needs 1/0 AWG copper or 3/0 AWG aluminum wire with 75 °C terminations.

150 amp wire size by termination rating

Wire size for a 150 amp circuit by termination temperature rating (60 °C: NM-B cable; 75 °C: THHN and most breakers), with the ground wire
Termination ratingCopperAluminum
60 °C3/0 AWG4/0 AWG
75 °C, THHN1/0 AWG3/0 AWG
Ground wire6 AWG4 AWG

150 amp wire size by distance at 240 V

Sizes that keep the voltage drop within 3% on a 240 V circuit loaded to the full 150 A, 75 °C terminations. The copper ground wire grows with the hot wires on long runs.

Wire size for a 150 amp, 240 V circuit by one-way distance, keeping the voltage drop within 3%
One-way distanceCopperDropCopper groundAluminumDrop
25 ft1/0 AWG0.4%6 AWG3/0 AWG0.4%
50 ft1/0 AWG0.8%6 AWG3/0 AWG0.8%
100 ft1/0 AWG1.5%6 AWG3/0 AWG1.6%
150 ft1/0 AWG2.3%6 AWG3/0 AWG2.4%
200 ft2/0 AWG2.4%4 AWG4/0 AWG2.5%
300 ft3/0 AWG2.9%4 AWG300 kcmil2.7%
3002504/03/02/01/00100200300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum3002504/03/02/01/0050100150200250300Wire size, AWG / kcmilOne-way distance, ft25 ft50 ft100 ft150 ft200 ft300 ftCopperAluminum
  • Copper
  • Aluminum
Wire size for 150 A at 240 V by distance, within 3% voltage drop.

Check your own 150 amp run

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
1/0 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
150 A
Voltage drop
1.8 V (0.8%)
Volts at the load
238.2 V
Ground wire
6 AWG copper

How it is calculated

  1. Breaker: 150 A rounded up to a standard size = 150 A.
  2. Smallest copper conductor rated for 150 A at 75 °C: 1/0 AWG.
  3. Drop = 2 × K × 150 A × 50 ft ÷ 105,600 cmil = 1.83 V, target 3% of 240 V.
Panel150 A240 V1/0 AWG copper50 ft one wayLoad238.2 V

What a 150 amp circuit is used for