Wire size for a 125 amp sub panel

Feed a 125 amp sub panel with 1 AWG copper or 2/0 AWG aluminum wire at 75 °C and a separate 6 AWG copper (4 AWG aluminum) ground.

125 amp sub panel feeder size

125 amp sub panel feeder at 75 °C and ground wire, copper and aluminum, and the smallest conduit for four THHN wires
CopperAluminum
Feeder, 75 °C1 AWG2/0 AWG
NM-B, 60 °Cnot made—
Ground wire6 AWG4 AWG
EMT conduit1-1/4″1-1/2″
PVC 40 conduit1-1/4″1-1/2″

Conduit sizes are for four THHN wires: two hots and a neutral of the feeder size plus the ground wire.

125 amp sub panel wire size by distance

Sizes that keep the voltage drop within 3% at 240 V with the panel fully loaded. When the feeder is made larger for distance, the ground wire grows with it, in copper and in aluminum.

125 amp sub panel feeder and ground wire by one-way distance, copper and aluminum at 75 °C, within 3% voltage drop at 240 V and full load
DistanceCopper feederCopper groundAluminum feederAluminum ground
50 ft1 AWG6 AWG2/0 AWG4 AWG
100 ft1 AWG6 AWG2/0 AWG4 AWG
150 ft1 AWG6 AWG2/0 AWG4 AWG
200 ft1/0 AWG4 AWG3/0 AWG2 AWG
300 ft3/0 AWG3 AWG250 kcmil1 AWG
2504/03/02/01/010100200300Feeder size, AWG / kcmilOne-way distance, ft50 ft100 ft150 ft200 ft300 ftCopper feederAluminum feeder2504/03/02/01/01050100150200250300Feeder size, AWG / kcmilOne-way distance, ft50 ft100 ft150 ft200 ft300 ftCopper feederAluminum feeder
  • Copper feeder
  • Aluminum feeder
125 amp sub panel feeder size by distance, within 3% voltage drop at 240 V.

A panel is rarely loaded to its full rating for long. Sizing for the actual calculated load instead of the breaker rating gives smaller wire on long runs; the calculator below does that.

What are you sizing for?
A
ft

From the panel to the load, not there and back

Voltage
Conductor
Termination rating
Result
1 AWG copper

Ampacity sets the size; the voltage drop is within 3%.

Breaker
125 A
Voltage drop
3.9 V (1.6%)
Volts at the load
236.1 V
Ground wire
6 AWG copper

How it is calculated

  1. Breaker: 125 A rounded up to a standard size = 125 A.
  2. Smallest copper conductor rated for 125 A at 75 °C: 1 AWG.
  3. Drop = 2 × K × 125 A × 100 ft ÷ 83,690 cmil = 3.85 V, target 3% of 240 V.
Panel125 A240 V1 AWG copper100 ft one wayLoad236.1 V