Wire size calculator
What are you sizing for?
A
ft
From the panel to the load, not there and back
Voltage
Conductor
Termination rating
Result
10 AWG copper
The run is long: ampacity alone allows 12 AWG, but a larger wire keeps the drop within 3%.
- Breaker
- 20 A
- Voltage drop
- 2.5 V (2.1%)
- Volts at the load
- 117.5 V
- Ground wire
- 10 AWG copper
How it is calculated
- Breaker: 20 A rounded up to a standard size = 20 A.
- Smallest copper conductor rated for 20 A at 75 °C: 12 AWG.
- Drop = 2 × K × 20 A × 50 ft ÷ 10,380 cmil = 2.49 V, target 3% of 120 V.