30 kVA to amps

On a 208 V three-phase system, 30 kVA draws 83.27 amps; at 480 V it draws 36.08 amps, and on 240 V single phase 125 amps.

30 kVA to amps at common voltages

30 kVA in amps by voltage
VoltageAmps, ABreaker, continuous load, A
240 V single phase125175
208 V three phase83.27110
240 V three phase72.17100
480 V three phase36.0850
050100150Amps, AVoltage240 V single phase240 V single phase, Amps: 125125208 V three phase208 V three phase, Amps: 83.2783.27240 V three phase240 V three phase, Amps: 72.1772.17480 V three phase480 V three phase, Amps: 36.0836.08
30 kVA in amps by voltage.

How to convert 30 kVA to amps

On a three-phase system, amps = kVA × 1,000 ÷ (1.732 × volts): 30 kVA × 1,000 ÷ (1.732 × 208 V) = 83.27 A per line. On single phase, amps = kVA × 1,000 ÷ volts: 30 kVA × 1,000 ÷ 240 V = 125 A.

The breaker column assumes a continuous load, sized at 125% of the current, and rounds up to the next standard breaker. Transformers and generators have their own protection rules; follow the nameplate.

Nearby values

Amps for 15 to 150 kVA at 208 V three phase and 480 V three phase
kVA208 V three phase, A480 V three phase, A
1541.6418.04
3083.2736.08
45124.9154.13
75208.1890.21
100277.57120.28
150416.36180.42

kVA to amps calculator

Convert
kVA
Voltage
Phase
Result
83.27 A

Full-load current on each line. Size breakers and conductors from the nameplate and the code, not from this figure alone.

Current per line
83.27 A
Breaker at 125% (continuous)
110 A

How it is calculated

  1. Amps = 30 kVA × 1,000 ÷ (208 V × √3) = 83.27