kVA to amps calculator

Amps = kVA × 1,000 ÷ volts for single phase, and kVA × 1,000 ÷ (√3 × volts) for three phase. A 75 kVA transformer on 208 V three phase delivers about 208 A.

Convert
kVA
Voltage
Phase
Result
208.18 A

Full-load current on each line. Size breakers and conductors from the nameplate and the code, not from this figure alone.

Current per line
208.18 A
Breaker at 125% (continuous)
300 A

How it is calculated

  1. Amps = 75 kVA × 1,000 ÷ (208 V × √3) = 208.18

How to calculate kVA to amps

kVA is volts × amps ÷ 1,000, so the current is the kVA × 1,000 divided by the voltage, and by √3 more on three phase. The worked numbers use the calculator's default: 75 kVA on 208 V three phase.

Step 1: three-phase kVA to amps

Amps = kVA × 1,000 ÷ (√3 × line-to-line volts)

I = S × 1,000 ÷ (1.732 × V)

Example 75 kVA × 1,000 ÷ (1.732 × 208 V) = 208.2 A on each line

Step 2: single-phase kVA to amps

Amps = kVA × 1,000 ÷ volts

I = S × 1,000 ÷ V

Example The same 75 kVA on 240 V single phase: 75 × 1,000 ÷ 240 V = 312.5 A

Step 3: kW to amps needs the power factor

Amps = kW × 1,000 ÷ (√3 × volts × power factor) on three phase; without √3 on single phase

kVA = kW ÷ power factor

Example 75 kW at a power factor of 0.8 on 208 V three phase: 75 × 1,000 ÷ (1.732 × 208 × 0.8) = 260.2 A

Step 4: breaker for a continuous load

Breaker ≥ full-load amps × 1.25, rounded up to the next standard size

Example 208.2 A × 1.25 → 300 A breaker

Transformer and generator protection has its own rules; take the final breaker size from the nameplate and the installation instructions.

kVA to amps chart

A 75 kVA load draws 208.2 A on each line at 208 V three phase, 90.2 A at 480 V three phase and 312.5 A at 240 V single phase.

Full-load current per line for 15 to 300 kVA at 240 V single phase and 208 V and 480 V three phase
kVAAmps, 240 V single phaseAmps, 208 V three phaseAmps, 480 V three phase
1562.541.618
3012583.336.1
45187.5124.954.1
75312.5208.290.2
112.5468.8312.3135.3
150625416.4180.4
225937.5624.5270.6
3001,250832.7360.8
02505007501,0001,2500100200300Current per line, AApparent power, kVA15304575112.5150225300240 V single phase208 V three phase480 V three phase
  • 240 V single phase
  • 208 V three phase
  • 480 V three phase
Current per line by kVA.

kVA, kW and amps

kVA is apparent power, the volts × amps a transformer or generator must deliver; kW is the real power. That is why converting kW to amps needs a power factor and converting kVA does not.

Transformers and generators are rated in kVA because the current they carry heats them whatever the power factor of the load.

Embed this calculator

Paste this code into your site or forum post to show the calculator. It works on any page that allows iframes. Preview the widget.