A 200 amp service for a house needs 2/0 AWG copper or 4/0 AWG aluminum service entrance wire, sized for 166 A (83% of 200 A). The grounding electrode conductor for a 200 amp service is 4 AWG copper, or 6 AWG copper when it runs only to ground rods.
200 amp service wire size
200 amp service entrance wire at 75 °C, copper and aluminum, and the smallest conduit for three THHN wires
Copper
Aluminum
House, 83%
2/0 AWG
4/0 AWG
Full rating
3/0 AWG
250 kcmil
EMT conduit
1-1/2″
2″
PVC 40 conduit
1-1/2″
2″
The full rating row is for a service that does not carry the whole load of one home. Conduit sizes are for three THHN wires of the service size: two hots and a full-size neutral. A smaller neutral, allowed in many cases, can reduce the conduit.
How the 200 amp service wire is sized
200 A × 0.83 = 166 A. The smallest wire rated for at least 166 A at 75 °C is 2/0 AWG copper (175 A) or 4/0 AWG aluminum (180 A). Without the 83% rule the same service would need 3/0 AWG copper or 250 kcmil aluminum.
The 83% sizing applies only to the 120/240 V single-phase wires that carry the whole load of one home. Where the wire also needs a correction for heat or bundling, such as a run through a hot attic or a conduit crowded with other circuits, it is sized for 83% of the rating divided by the correction factor, which can mean one size larger.
Ground wire size for a 200 amp service
Grounding electrode conductor for a 200 amp service with 2/0 AWG copper service wire: to a metal water pipe or building steel, or to ground rods only
Runs to
Copper
Aluminum
Water pipe, steel
4 AWG
2 AWG
Ground rods only
6 AWG
not used
Aluminum grounding electrode conductor may not be terminated within 18 in. of the earth outside a building or listed enclosure, and a ground rod clamp sits at the earth, so the wire to ground rods is copper. Aluminum is used only where it runs to a connection above that height, such as a water pipe or building steel.
Who sizes the service wire
The utility decides the size of its own drop or lateral and the meter equipment. The service entrance wire from the meter to the main panel is the owner's, and the local inspector checks it. Many utilities publish their own requirements; check them before buying wire.
Typical 200 amp service uses
Most new single-family houses
Houses with central air, an electric range and dryer