How many 10 gauge wires fit in 1/2 inch conduit?

A 1/2 inch EMT conduit holds up to 5 THHN wires of 10 AWG at 40% fill (NEC 2023, Chapter 9 Table 1). The same trade size holds 5 wires in PVC Schedule 40, 4 in PVC Schedule 80 and 6 in rigid metal conduit (RMC).

10 AWG THHN wires in 1/2 inch conduit by conduit type

10 AWG THHN wires in 1/2 inch conduit at 40% fill
ConduitInside area, in²10 AWG THHN wires
Electrical metallic tubing (EMT)0.3045
Rigid PVC conduit, Schedule 400.2855
Rigid PVC conduit, Schedule 800.2174
Rigid metal conduit (RMC)0.3146

How the 40% conduit fill is calculated

Wires = inside area × 40% ÷ area of one wire. One 10 AWG THHN wire is 0.0211 in². In 1/2 inch EMT: 0.304 in² × 40% ÷ 0.0211 in² = 5.76, rounded down unless the decimal is 0.8 or more, so 5 wires.

When 1/2 inch conduit runs out of room for 10 AWG wire

A single 240 V, 30 amp circuit needs two hots and a ground, which fits easily. Adding a neutral or a second circuit is where half-inch conduit runs out of room.

The wire counts on this page are for THHN/THWN-2 insulation. PVC Schedule 80 has the thickest wall and the smallest inside area of the common types.