How many 10 gauge wires fit in 3/4 inch conduit?
A 3/4 inch EMT conduit holds up to 10 THHN wires of 10 AWG at 40% fill (NEC 2023, Chapter 9 Table 1). The same trade size holds 9 wires in PVC Schedule 40, 7 in PVC Schedule 80 and 10 in rigid metal conduit (RMC).
10 AWG THHN wires in 3/4 inch conduit by conduit type
| Conduit | Inside area, in² | 10 AWG THHN wires |
|---|---|---|
| Electrical metallic tubing (EMT) | 0.533 | 10 |
| Rigid PVC conduit, Schedule 40 | 0.508 | 9 |
| Rigid PVC conduit, Schedule 80 | 0.409 | 7 |
| Rigid metal conduit (RMC) | 0.549 | 10 |
How the 40% conduit fill is calculated
Wires = inside area × 40% ÷ area of one wire. One 10 AWG THHN wire is 0.0211 in². In 3/4 inch EMT: 0.533 in² × 40% ÷ 0.0211 in² = 10.1, rounded down unless the decimal is 0.8 or more, so 10 wires.
What 10 AWG wires in 3/4 inch conduit usually carry
10 AWG wire feeds 30 amp loads such as dryers, water heaters and small air conditioners. Each 240 V circuit uses two hot conductors, and a ground wire counts toward the fill as well.
With more than three current-carrying conductors in one conduit, their ampacity must be reduced. The wire counts on this page are for THHN/THWN-2 insulation.