100 kW to amps

On a 208 V three-phase system, 100 kW draws 277.57 amps; at 480 V it draws 120.28 amps, and on 240 V single phase 416.67 amps at a power factor of 1.

100 kW to amps at common voltages

100 kW in amps by voltage, power factor 1
VoltageAmps, ABreaker, continuous load, A
240 V single phase416.67over 400
208 V three phase277.57350
240 V three phase240.56350
480 V three phase120.28175
0200400600Amps, AVoltage240 V single phase240 V single phase, Amps: 416.67416.67208 V three phase208 V three phase, Amps: 277.57277.57240 V three phase240 V three phase, Amps: 240.56240.56480 V three phase480 V three phase, Amps: 120.28120.28
100 kW in amps by voltage.

How to convert 100 kW to amps

On a three-phase system, amps = kW × 1,000 ÷ (1.732 × volts × power factor): 100 kW × 1,000 ÷ (1.732 × 208 V × 1) = 277.57 A per line. At a power factor of 0.8, the same 100 kW draws 346.97 A. On single phase, amps = kW × 1,000 ÷ (volts × power factor): 100 kW × 1,000 ÷ 240 V = 416.67 A at a power factor of 1.

The breaker column assumes a continuous load, sized at 125% of the current, and rounds up to the next standard breaker. Transformers and generators have their own protection rules; follow the nameplate.

Nearby values

Amps for 5 to 100 kW at 208 V three phase and 480 V three phase
kW208 V three phase, A480 V three phase, A
513.886.01
1027.7612.03
2055.5124.06
50138.7960.14
100277.57120.28

kW to amps calculator

Convert
kW
Voltage
Phase
Result
277.57 A

Full-load current on each line. Size breakers and conductors from the nameplate and the code, not from this figure alone.

Current per line
277.57 A
Breaker at 125% (continuous)
350 A

How it is calculated

  1. Amps = 100 kW × 1,000 ÷ (208 V × √3 × 1) = 277.57