5 kW to amps

On a 208 V three-phase system, 5 kW draws 13.88 amps; at 480 V it draws 6.01 amps, and on 240 V single phase 20.83 amps at a power factor of 1.

5 kW to amps at common voltages

5 kW in amps by voltage, power factor 1
VoltageAmps, ABreaker, continuous load, A
240 V single phase20.8330
208 V three phase13.8820
240 V three phase12.0320
480 V three phase6.0115
0102030Amps, AVoltage240 V single phase240 V single phase, Amps: 20.8320.83208 V three phase208 V three phase, Amps: 13.8813.88240 V three phase240 V three phase, Amps: 12.0312.03480 V three phase480 V three phase, Amps: 6.016.01
5 kW in amps by voltage.

How to convert 5 kW to amps

On a three-phase system, amps = kW × 1,000 ÷ (1.732 × volts × power factor): 5 kW × 1,000 ÷ (1.732 × 208 V × 1) = 13.88 A per line. At a power factor of 0.8, the same 5 kW draws 17.35 A. On single phase, amps = kW × 1,000 ÷ (volts × power factor): 5 kW × 1,000 ÷ 240 V = 20.83 A at a power factor of 1.

The breaker column assumes a continuous load, sized at 125% of the current, and rounds up to the next standard breaker. Transformers and generators have their own protection rules; follow the nameplate.

Nearby values

Amps for 5 to 100 kW at 208 V three phase and 480 V three phase
kW208 V three phase, A480 V three phase, A
513.886.01
1027.7612.03
2055.5124.06
50138.7960.14
100277.57120.28

kW to amps calculator

Convert
kW
Voltage
Phase
Result
13.88 A

Full-load current on each line. Size breakers and conductors from the nameplate and the code, not from this figure alone.

Current per line
13.88 A
Breaker at 125% (continuous)
20 A

How it is calculated

  1. Amps = 5 kW × 1,000 ÷ (208 V × √3 × 1) = 13.88