Drain pipe size chart by fixture

A shower needs a 1-1/2 inch drain under the IPC. The minimum trap and drain size of each plumbing fixture and its drainage fixture units (DFU), as the International Plumbing Code (IPC) and the Uniform Plumbing Code (UPC) set them, from published state and local government documents; check the code your state and city use.

Minimum trap size in inches and drainage fixture units of household fixtures under the IPC and the UPC, as printed in the documents below
FixtureIPC trap, inIPC DFUUPC trap, inUPC DFU
Shower1-1/2222
Bathtub1-1/221-1/22
Toilet—333
Bathroom sink1-1/411-1/41
Kitchen sink1-1/221-1/22
Washing machine2223
Laundry or utility sink1-1/221-1/22
Dishwasher1-1/221-1/22
Floor drain2222

Shower, IPC: North Carolina's 2024 plumbing code requires a 2 inch shower trap instead.

Minimum slope of a horizontal drain by size

Minimum slope of horizontal drainage pipe in inches per foot by pipe diameter under the IPC and the UPC, as printed
CodePipe diameterMinimum slope, in/ftPercent
IPCUp to 2-1/2 in1/42.08%
IPC3 to 6 in1/81.04%
IPC8 in and larger1/160.52%
UPCAny size 1/8 in per foot for 4 in and larger pipe when approved1/42.08%

For the fall over a run, or to check a measured slope, use the drain slope calculator.

Which states use the IPC and which the UPC

UPC: AK, CA, HI, IA, ID, MN, MT, NM, OR, WA. IPC: CO, FL, GA, IN, LA, MD, MI, NC, NY, OH, PA, TN, UT, VA. Cities and counties can adopt their own code or amendments; ask the local building department.