Drain pipe size chart by fixture
A shower needs a 1-1/2 inch drain under the IPC. The minimum trap and drain size of each plumbing fixture and its drainage fixture units (DFU), as the International Plumbing Code (IPC) and the Uniform Plumbing Code (UPC) set them, from published state and local government documents; check the code your state and city use.
| Fixture | IPC trap, in | IPC DFU | UPC trap, in | UPC DFU |
|---|---|---|---|---|
| Shower | 1-1/2 | 2 | 2 | 2 |
| Bathtub | 1-1/2 | 2 | 1-1/2 | 2 |
| Toilet | — | 3 | 3 | 3 |
| Bathroom sink | 1-1/4 | 1 | 1-1/4 | 1 |
| Kitchen sink | 1-1/2 | 2 | 1-1/2 | 2 |
| Washing machine | 2 | 2 | 2 | 3 |
| Laundry or utility sink | 1-1/2 | 2 | 1-1/2 | 2 |
| Dishwasher | 1-1/2 | 2 | 1-1/2 | 2 |
| Floor drain | 2 | 2 | 2 | 2 |
Shower, IPC: North Carolina's 2024 plumbing code requires a 2 inch shower trap instead.
Minimum slope of a horizontal drain by size
| Code | Pipe diameter | Minimum slope, in/ft | Percent |
|---|---|---|---|
| IPC | Up to 2-1/2 in | 1/4 | 2.08% |
| IPC | 3 to 6 in | 1/8 | 1.04% |
| IPC | 8 in and larger | 1/16 | 0.52% |
| UPC | Any size 1/8 in per foot for 4 in and larger pipe when approved | 1/4 | 2.08% |
For the fall over a run, or to check a measured slope, use the drain slope calculator.
Which states use the IPC and which the UPC
UPC: AK, CA, HI, IA, ID, MN, MT, NM, OR, WA. IPC: CO, FL, GA, IN, LA, MD, MI, NC, NY, OH, PA, TN, UT, VA. Cities and counties can adopt their own code or amendments; ask the local building department.