Drain slope calculator
Fall = slope × length. A drain sloped 1/4 inch per foot falls 5 inches over 20 feet; at 1/8 inch per foot, 2.5 inches. The International Plumbing Code asks for at least 1/4 inch per foot on drains up to 2.5 inches and 1/8 inch per foot from 3 to 6 inches; the Uniform Plumbing Code asks for 1/4 inch per foot, with 1/8 inch allowed on 4-inch and larger drains when the inspector approves.
A 2 inch drain 20 ft long at 1/4 in per foot falls 5 in (2.08%); the IPC minimum for this size is 1/4 in per foot, a 5 in fall, so this slope is enough.
- Slope, percent
- 2.08%
- IPC minimum
- 1/4 in/ft
- Minimum fall over this run
- 5 in
- Meets the minimum
- Yes
How it is calculated
- Fall = slope × run = 0.25 in/ft × 20 ft = 5 in.
- Percent = in per foot ÷ 12 × 100 = 2.083%.
- IPC minimum for 0–2.5 in drains: 1/4 in/ft (NC Building Code Council).
How to calculate drain slope and fall
The worked numbers use the calculator's default: a 2 inch drain 20 ft long at 1/4 inch per foot.
Step 1: Fall over the run
Fall (in) = slope (in/ft) × length (ft)
Example 0.25 × 20 = 5 in
Step 2: Slope from a measured fall
Slope (in/ft) = fall (in) ÷ length (ft)
Percent = slope ÷ 12 × 100
Example 5 ÷ 20 = 0.25 in/ft
Example 0.25 ÷ 12 × 100 = 2.08%
Drain fall by length at 1/16, 1/8 and 1/4 inch per foot
How far a horizontal drain drops over common run lengths at each slope the codes use. Multiply the slope by the length for any other run.
| Run, ft | 1/16 in/ft | 1/8 in/ft | 1/4 in/ft |
|---|---|---|---|
| 5 ft | 0.31 in | 0.63 in | 1.25 in |
| 10 ft | 0.63 in | 1.25 in | 2.5 in |
| 15 ft | 0.94 in | 1.88 in | 3.75 in |
| 20 ft | 1.25 in | 2.5 in | 5 in |
| 25 ft | 1.56 in | 3.13 in | 6.25 in |
| 30 ft | 1.88 in | 3.75 in | 7.5 in |
| 40 ft | 2.5 in | 5 in | 10 in |
| 50 ft | 3.13 in | 6.25 in | 12.5 in |
| 75 ft | 4.69 in | 9.38 in | 18.75 in |
| 100 ft | 6.25 in | 12.5 in | 25 in |
Why drains need a minimum slope
A horizontal drain carries waste by gravity, so it needs enough fall for water to move the solids along. Smaller pipes need a steeper slope than larger ones in the codes, which is why the minimum drops from 1/4 to 1/8 inch per foot as the pipe gets bigger.
Check which code your state and city use: the minimums differ between the IPC and the UPC, and local amendments can change them. Measure the fall with a level and a tape over a known length, then use the "Check a slope" mode.