Copper pipe size chart
Copper tube from 1/4 to 4 inch runs from 0.375 to 4.125 in outside diameter (9.5 to 104.8 mm), with Type K, Type L, Type M, DWV for each size. Copper tube uses copper tube sizes (CTS): Types K, L and M of one nominal size share the outside diameter and differ in wall thickness.
| Nominal size | OD, in | OD, mm | Type K wall, in | Type K ID, in | Type L wall, in | Type L ID, in | Type M wall, in | Type M ID, in | DWV wall, in | DWV ID, in | Type L gallons per foot |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1/4″ | 0.375 | 9.5 | 0.035 | 0.305 | 0.030 | 0.315 | — | — | — | — | 0.004 |
| 3/8″ | 0.500 | 12.7 | 0.049 | 0.402 | 0.035 | 0.430 | 0.025 | 0.450 | — | — | 0.0075 |
| 1/2″ | 0.625 | 15.9 | 0.049 | 0.527 | 0.040 | 0.545 | 0.028 | 0.569 | — | — | 0.0121 |
| 5/8″ | 0.750 | 19.0 | 0.049 | 0.652 | 0.042 | 0.666 | — | — | — | — | 0.0181 |
| 3/4″ | 0.875 | 22.2 | 0.065 | 0.745 | 0.045 | 0.785 | 0.032 | 0.811 | — | — | 0.0251 |
| 1″ | 1.125 | 28.6 | 0.065 | 0.995 | 0.050 | 1.025 | 0.035 | 1.055 | — | — | 0.0429 |
| 1-1/4″ | 1.375 | 34.9 | 0.065 | 1.245 | 0.055 | 1.265 | 0.042 | 1.291 | 0.040 | 1.295 | 0.0653 |
| 1-1/2″ | 1.625 | 41.3 | 0.072 | 1.481 | 0.060 | 1.505 | 0.049 | 1.527 | 0.042 | 1.541 | 0.0924 |
| 2″ | 2.125 | 54.0 | 0.083 | 1.959 | 0.070 | 1.985 | 0.058 | 2.009 | 0.042 | 2.041 | 0.1608 |
| 2-1/2″ | 2.625 | 66.7 | 0.095 | 2.435 | 0.080 | 2.465 | 0.065 | 2.495 | — | — | 0.2479 |
| 3″ | 3.125 | 79.4 | 0.109 | 2.907 | 0.090 | 2.945 | 0.072 | 2.981 | 0.045 | 3.030 | 0.3539 |
| 3-1/2″ | 3.625 | 92.1 | 0.120 | 3.385 | 0.100 | 3.425 | 0.083 | 3.459 | — | — | 0.4786 |
| 4″ | 4.125 | 104.8 | 0.134 | 3.857 | 0.110 | 3.905 | 0.095 | 3.935 | 0.058 | 4.009 | 0.6222 |
- Outside diameter
- Type K inside diameter
- Type L inside diameter
- Type M inside diameter
Why a 1 inch copper pipe is not 1 inch across
The nominal size is a trade name, not a measurement. 1 inch copper pipe measures 1.125 in outside and 1.025 in inside at Type L. Copper tube uses copper tube sizes (CTS): Types K, L and M of one nominal size share the outside diameter and differ in wall thickness. To match a fitting, compare outside diameters; to work out how much water a pipe holds, use the inside diameter.
How to measure copper pipe to find its size
Measure the outside diameter: calipers across the widest point, or a tape wrapped once around the pipe divided by 3.1416. Find the nearest outside diameter in the chart; the print on the pipe gives the type. The pipe size identifier matches a measurement against every material at once. For the water a run holds, use the pipe volume calculator.